380V 68KW Total Heat Recovery Modular Air Cooled Chiller
Features
1. Copeland scroll compressor or Danfoss scroll compressor
2. Plate heat exchanger or shell tube heat exchanger
3. Modular design , max 16 units work together
4. Industrial cooling application , and min -10 C outlet
temperature
5. Outlet temperature control
6. EVI compressor fow low ambient temp , min -25 C ambient
temperature for heating ;
7. Total heat recovery
The EKAC series full heat recovery modular air-cooled heat pump
unit introduces the design and development essence of European
total heat recovery technology, and perfectly combines the
air-cooled chiller unit with the air source heat pump water heater
unit. In addition to cooling in summer and heating in winter, the
unit can also produce domestic hot water at 40°C to 50°C around the
clock. It can replace the hot water boiler, saving investment in
hot water boiler and machine room. This not only protects the
environment, but also saves operating costs. The unit can recover
the waste heat released by refrigeration, effectively avoiding the
"heat island effect";
Specifications:
Model: | EKAC230 | |||
BR1SRM/S | ||||
Air conditioning mode | Nominal cooling capacity | kW | 68 | |
Nominal heating capacity | kW | 74 | ||
Total power of nominal cooling capacity | kW | 20.5 | ||
Nominal cooling operation current | A | 37.8 | ||
Total power of nominal heating capacity | kW | 21 | ||
Nominal heating operation current | A | 38.5 | ||
Water flow | Nominal cooling capacity | m³/h | 11.7 | |
Nominal heating capacity | m³/h | 12.7 | ||
Performance parameter | W/W | 3.32 | ||
Hot Water Mode | Circular water flow | m³/h | 14.1 | |
Nominal heating capacity | kW | 82 | ||
Total power of nominal hot water provision capacity | kW | 20.5 | ||
Cooling + Hot Water Mode | Nominal cooling capacity | kW | 64.5 | |
Nominal heat recovery capacity | kW | 84 | ||
Total nominal power | kW | 19.5 | ||
Water flow | Hot water | m³/h | 14.1 | |
Chilled water at air conditioning side | m³/h | 11.7 |
Note:
■ Cooing capacity tested on : chilled water outlet temperature 7°C
, water flow: 0.172m3/(h·kW),outdoor temperature 35 °C ;
■ Heating capacity: hot water outlet temperature 45°C ,water flow:
0.172m3/(h·kW) ,outdoor dry/web bulb temperature 7°C/6°C;
Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
EUROKLIMAT (EK) was established in 1963 in Italy. For the past half a century, it has become famous as an energy-saving air-conditioning manufacturer in Italy and globally. Continuous innovation, new product development and top manufacturing quality are the driving force behind this growth.
EUROKLIMAT (EK) pursues the ideals of protecting the environment, providing physical comfort and adopting energy-saving into the whole process of product R&D, manufacturing and service. Our products covering residential, commercial and close control air-conditioner are manufactured according to the global generally accepted standards.